The tag worksheet — for Engineering / Controls

Hand this page to whoever knows the machines and the PLC tags. What comes back is one CSV row per machine — that single file configures the whole MES.

What we are building

A monitoring layer that watches each machine's existing tags — nothing is added to any PLC — and turns them into downtime history, OEE and trends. It is read-only: it subscribes to the tags you list and writes to none.

For each machine on the line we need four tag addresses and two facts. Blank is a legitimate answer everywhere except the state tag — the software shows unknown rather than inventing a number.

The worksheet columns

Fill one row per machine, in process order (upstream first — row order becomes the routing). Template: worksheet-template.csv; a filled example: worksheet-example.csv.

column what goes in it
equipment Short code for the machine — FIL01, CAP01. No spaces. This becomes its name in the MES.
name Human name — "Filler 1". Shown on every dashboard.
node_state Full OPC node id of the tag that says what the machine is doing.
node_good Node id of the cumulative good-parts counter.
node_scrap Node id of the cumulative reject counter. Blank if the machine has none.
node_analog Node id of one process value worth trending — a temperature, pressure, torque, speed.
analog_name What that value is called — FillTemp, CapTorque.
state_map What each raw state value means: 0=idle; 1=running; 4=down; 5=setup
cycle_seconds Rated seconds per unit at this machine. Blank if not known.
notes Anything worth keeping. Not read by software.

Finding node ids

In Kepware a tag's id is Channel.Device.TagName — the tree you see in the configuration client — carried in a node id like:

ns=2;s=Line1.Filler.ProdCount

ns=2 is Kepware's default namespace index. The reliable way to get ids exactly right is OPC Quick Client (Kepware: Tools → Launch OPC Quick Client): click a tag and copy its Item ID. Watch for auto-generated tag names that differ from the display name — e.g. tags generated from a file keep the sanitised file name in them (LD_csv_State). We will verify every id against the live server before trusting any of them, so a typo is caught, not fatal.

The two answers that matter most

1. What do the state values mean — and which ones count as down?

This is the decision with real consequences, because it defines every availability figure the system will ever report:

the machine is... map it to why
producing running
stopped, no product to work on (starved) idle the machine is healthy — the line has a problem
stopped, downstream full (blocked) idle same
faulted / breakdown down the only thing that should count against availability
changeover / planned stop setup not downtime — mapping this to down silently wrecks OEE

If a changeover gets mapped to down, every availability number reported afterwards is wrong, and nobody will be able to say why. If a value ever shows up that is not in your map, the system flags it loudly rather than guessing.

2. How do the counters behave?

We book production from counter increases, so we need cumulative counters, and we need to know their habits:

  • Do they reset — at shift change, at power cycle, at order change? (Resets are handled: the count re-baselines and nothing false is booked. We just should not be surprised by them.)
  • What do they count — bottles, cases, trays? Per-machine differences are fine; say so in notes.
  • Is scrap counted at all? Many machines only count good. Then leave node_scrap blank and that machine's quality reads unknown — which is the truth, and better than pretending zero scrap.

The cycle time

cycle_seconds is the machine's rated time per unit — nameplate speed or the standard from the process sheet. It is the denominator of OEE performance ("how fast did it run vs. how fast should it"). If nobody is sure, leave it blank: performance will show unknown until the real number is filled in. A guessed cycle time is worse than none, because it quietly turns performance into fiction.

What happens with the worksheet

  1. fsmes make-tag-map worksheet.csv turns it into the MES configuration, flagging anything inconsistent.
  2. fsmes opc-verify connects to the server and reads every listed tag twice — you can watch the same values in OPC Quick Client while it runs. Anything unreadable or unmappable is reported per tag, with the machine and id.
  3. The line appears on the dashboards. From then on, changing which tags feed the MES means editing the worksheet and regenerating — never code.