Explanation — what happens when the MES loses sight of a machine¶
A plant loses its connection to the machine layer most weeks. A switch reboots, a certificate expires, an engineer unplugs the wrong port, a PLC is swapped. The line does not stop. The machines are fine. The MES just cannot see any of it.
This page is what this MES does about that, and — more usefully — what it refuses to do. The decision behind it is 0030.
The two wrong answers¶
They are symmetrical, and both survive for years because the number still looks plausible.
Read the gap as a stop. The machine goes into down for the length of
the outage. Now the plant has a breakdown that never happened, on a machine
that was running the whole time, and somebody walks out to look at it.
Read it as the last state we heard. The machine stays running — or
down, or whatever it was — until the link comes back. Now the plant has
availability nobody was watching. This is the worse of the two, because it
reads better, so it is believed. It is also what this MES did before
2026-09-14: the agent logged the dropped connection and slept, the open
state interval stayed open, and the invented run time went straight into
availability's numerator and the machine's maintenance hours.
What it does instead¶
The connection is its own history. equipment_connections holds one row
per contiguous stretch of being able — or unable — to see a machine, the same
shape equipment_states has. A machine can be down and reachable or fine
and unreachable, and a plant that has to pick one column for both has thrown
away the more useful half.
The state history stops where the evidence stops. When the agent records
a disconnection it closes the machine's open state interval at the last
moment there was evidence, and opens nothing in its place. For the length of
the outage the machine has no state, so every screen and every API
answers unknown — the word they already use for a machine they have no
interval for. Nothing carries on accruing: not run time, not downtime, not
maintenance hours.
Two timestamps, because the difference is real. Each interval carries
started_at — the last moment there was positive evidence of the link — and
detected_at, when the agent noticed. The server may have gone at either end
of the seconds between them, so both are recorded and neither is averaged
into the other.
Unknown time leaves the denominator. Availability is run time ÷
observed time, where observed time is the window less the seconds this
machine was disconnected inside it. Every OEE answer carries
unknown_seconds and unknown_share beside the figure, so 92 % availability
over forty observed minutes of an eight-hour window cannot be read as though
it covered the shift. The downtime pareto states the unknown share of its
window for the same reason the unlabelled bucket exists — and since 2026-09-29
out of the coverage ledger rather than out of the disconnection rows, so a
pareto over a window this MES has no history for says so instead of reporting
nothing unwatched.
A disconnection is never a downtime reason. It is not a bucket in the pareto, it does not book, it does not label a stop, and it never reaches an ERP confirmation as a stop.
How it is detected¶
Positively. The agent asks the server whether the session is still alive every
opc_health_periods publish intervals — three by default, so about a second
and a half on a real line, and never faster than once a second. Losing the
client session is the other trigger.
Silence from a tag is not a trigger, and this is worth being clear about because it is the obvious thing to do and it is wrong. OPC UA notifies on change. A machine standing idle correctly sends nothing for an hour. Inferring an outage from that invents one, which is the same fault as missing a real one, in the other direction. When a plant's server publishes a real heartbeat tag, per-equipment staleness becomes a positive signal and this MES should use it; not before.
What you will see¶
| Where | What it says |
|---|---|
| Floor tiles, line view | the machine's tile in the grey the product uses for unknown, with a dashed edge, and a strip saying no connection since 09:12 — the OPC server did not answer |
| Machine page | the same, in place of the state pill and its "since" line |
| State timeline | the outage drawn as its own interval, rather than as white space — a hole in a Gantt reads as nothing happened, and this one means nobody was looking |
GET /equipment/connections |
every machine, its connection, since when and why, with the total stated |
GET /health |
a watching block: machines, connected, disconnected, and how many have no connection fact at all |
| Fleet console | a Watching column, so a plant that is up and blind to nine machines cannot hide behind the light that says it is up |
| The namespace | an equipment_connection_change event, so a subscriber knows when the last state it heard stopped meaning anything |
unknown in that list is not a failure to answer. It means nothing has ever
reported a connection for that machine — a machine fed by hand, or over MQTT,
or one whose agent has never run. Calling it connected would be a claim
nobody made.
What this does not solve¶
An agent that is killed outright writes nothing. kill -9, a power cut
on the box the agent runs on, a container evicted: no disconnection is
recorded, so those machines' state intervals stay open and their last state
stands until something closes it. That is the old behaviour, still present in
that one case.
Closing it needs a heartbeat the API can read and time out on its own — the
agent saying "I am still here" often enough that the API can decide it is
not. That is a bigger change than this one and it is not made. Until it is,
the practical answer is the one every plant already uses: watch the agent
process, and alert on /health saying the plant can see fewer machines than
it has.
A server that answers but says nothing is not detected either. The session is alive, so the watchdog is satisfied; only a heartbeat tag or a publish-rate expectation would catch it, and both belong with the change above.
Units the machine counted during the outage are not booked. This one is worth knowing before you read a shift total. The agent books production from the increase of a cumulative counter, and its memory of the last value lives with the connection — so the first reading after a reconnect starts a fresh baseline, and whatever the counter climbed while nobody was watching books nothing. Measured: in a scripted run with two outages totalling seven minutes of line time, the line counted about 520 units per station inside them and the MES booked 306 to 337 fewer than the line made, on every station.
Nothing is invented and nothing is double-counted, which is the rule that outranks the others, but the shortfall is real and it is silent on the shift screen. It is not settled here because it is a second question and not a smaller one: those units happened, so decision 0019 says book them — and nothing can say when inside the gap they were made, nor which order they belong to if the line changed order during it. Until there is a record that settles it, the honest reading of a shift that contained an outage is: the unknown share on the OEE answer says how long nobody was watching, and the units counted in that time are not in the total.