How-to. Commissioning against a server that is already serving another system, without disturbing it.

At a real plant the OPC UA server exists, it is already feeding the system in charge, and somebody else administers it. Your job is to become one more read-only client on it and then prove your tag map is right. That is five things to ask for, four commands, and one certificate step that always fails the first time on purpose.

Nothing on this page writes to that server.

What to ask the server's owner for

Send them the OPC UA access request, which is written to be handed over as-is. It asks for five things:

  1. The endpoint URL — opc.tcp://<host>:<port>. Not the vendor's configuration or administration port, which is usually a different service on a different port and will answer with a connection reset.
  2. Confirmation the OPC UA interface is enabled. On some servers it ships off.
  3. The security policy the endpoint offers — commonly Basic256Sha256 with SignAndEncrypt. If theirs is different, they have to tell you, because the client asks for exactly what it is configured to ask for.
  4. A dedicated account with Browse and Read only. Ask for read-only in writing. It is the cheapest guarantee either side gets, it is enforced by their server rather than by your good intentions, and it makes the rest of the conversation short.
  5. One client certificate trusted — the step below.

Plus, if a firewall is in the path: TCP from the MES machine to the endpoint's host and port.

What the subscription costs their server

Say this before they ask. One client session. Roughly four monitored items per machine — a state tag, two counters and one process value — at a publishing interval of 500 ms (MES_OPC_PUBLISH_MS, and 1000 ms is fine if they would rather). No configuration API, no project changes, no browsing after commissioning. That is a rounding error on a server class that carries thousands of items, and saying the number is more convincing than saying "negligible".

What this MES will not do to their server

Worth putting in the same email, because it is what they are actually worried about:

  • It does not write. A tag map generated from the worksheet marks every machine read-only (order_tag: null), and with no write target configured there is no code path that writes to a tag.
  • It does not touch the project. No configuration API, no tags added, no users of ours on their server.
  • Revoking is one click. Untrust the certificate and the session stops. Nothing of ours persists on their side except that trust.

Two other outbound paths exist in this MES and are separate settings you should check before pointing it at a real plant: MES_ERP_MODE decides whether anything is posted to an ERP (off and file reach no live system), and MES_UNS_MODE is off by default so no MQTT broker is contacted. They are not part of the OPC conversation, but they are part of the same promise.

Set the connection up

In .env:

MES_OPC_ENDPOINT=opc.tcp://their-server:49320
MES_OPC_SECURITY=Basic256Sha256,SignAndEncrypt
MES_OPC_USER=the-read-only-account
MES_OPC_PASSWORD=...
MES_TAG_MAP_FILE=config/tag_map_plant.json

MES_OPC_SECURITY empty means anonymous and unencrypted, which is what the bundled simulator uses and what no real server offers. Setting it turns on the certificate handshake.

The certificate step

The client mints its own self-signed certificate the first time it needs one, into MES_OPC_CERT_DIR (default certs/):

certs/mes_twin_client.der
certs/mes_twin_client_key.pem

It is valid for ten years, its subject common name is MES-TWIN Agent, and its subject-alternative-name URI matches MES_OPC_APPLICATION_URI (urn:mes-twin:agent by default) — a UA server rejects a certificate whose SAN URI disagrees with the application URI the client advertises, so change one and you must change the other.

The first connection is rejected. That is the protocol working. Their server has never seen this certificate, so it refuses it and files it under rejected certificates; that refusal is how the certificate gets to their side. They then trust it, and the second attempt succeeds. Run a browse or a verify once, tell them it has arrived, and wait.

If you see BadCertificateUntrusted or BadSecurityChecksFailed, that is this and nothing else — the CLI says so rather than printing a bare status code. The other symptoms are in the access request's troubleshooting table.

Back the certificate up

Losing certs/ means minting a new certificate, which means going back to the server's owner for another trust step and another change window. fsmes backup copies it. This is the single most annoying thing to lose on a plant PC.

Look at what the server actually exposes

fsmes opc-browse --contains Filler
fsmes opc-browse --depth 4

It walks the address space under Objects/ and prints the browse name, the current value and the full node id of everything it finds, plus the server's namespace table. --contains filters by substring, which is what makes it usable on a real server with thousands of nodes; --depth defaults to 3.

This is where worksheet typos surface: the node id you were given and the node id the server has differ by a character, or by a namespace index, or the tag was auto-generated with a sanitised name that is not the display name. Exit code 2 means it could not connect at all — that is the certificate or the credentials, not the tag map.

Browse once, at commissioning. Nothing browses afterwards.

Draft the tag map from the worksheet

The tag map is not written by hand. It comes from a one-page CSV that whoever knows the machines fills in — one row per machine, four node ids and two facts. The columns, and what a blank in each of them costs you, are in the Engineering worksheet guide; the template is worksheet-template.csv and a filled example is worksheet-example.csv.

fsmes make-tag-map worksheet.csv --out config/tag_map_plant.json

It refuses anything it could not honestly interpret and exits 1 saying what. For every blank that has a consequence it prints a note rather than a default — no scrap counter means quality reads unknown, no cycle time means performance reads unknown. That is the point: a guessed cycle time turns performance into fiction quietly, and a blank turns it into unknown loudly.

The decision that matters most in that file is which state values count as down. A changeover mapped to down wrecks every availability figure the system will ever report, and nobody will be able to say why. Spend the time there.

If the line publishes the order it is running

Many line-control PLCs publish the current order somewhere — a register on a line object, not on any one machine. Without it this MES infers which order a unit belongs to from what it has released, which is a reasonable guess and still a guess. If that tag exists, name it and the guess stops:

"line": {
  "object": "Line",
  "publishes_order": "OrderId",
  "order_code": "WO-ACME-{value}"
}
  • publishes_order is read, never written. It is the opposite of a machine's order_tag, which is the MES pushing an order code down to a machine. Reading it takes one more subscribed item and keeps the promise in What this MES will not do to their server exactly as it is: a historian or a server you have no write rights on can still answer this.
  • order_code is the translation, because the two sides name the same order differently and always will: the PLC publishes 4711 in an integer register and this MES holds WO-ACME-4711. {value} is whatever the line published. A line that publishes the code outright writes "{value}".

Leave the block out if there is no such tag. Nothing degrades — the MES infers as it did before, and anything reading the block says unknown rather than inventing a join.

Prove the map before trusting it

fsmes opc-verify --seconds 15

It resolves every tag in the map through the agent's own resolution code — the same code that will run in production, so a map that verifies is a map the agent can read — then reads everything twice, --seconds apart, and reports per machine and per tag:

  • readable? the tag resolved and returned a value;
  • changing? the value moved between the two reads;
  • do the State values map? every observed raw state value is in the worksheet's state_map.
PASS: every mapped tag is readable and every observed State value maps.

Exit codes: 0 pass, 1 at least one tag unreadable or a State value with no mapping — the agent would misbehave with this map — and 2 could not connect.

Run it while the line is running. A stopped line makes every counter look static and every state look correct, and "changing?" is the column that catches a counter pointed at the wrong machine.

Re-run it whenever the worksheet changes. It is the regression test for the one file that decides what every number means.

Then give the MES its equipment

fsmes init-db
fsmes seed-line LINE1 --line-name "Filling Line 1" --site SITE1 --site-name "Main Site"

Stations, names and cycle times come out of the same tag map, so the equipment model and the subscription cannot disagree. --no-routing observes only: states, downtime and trends, with no production booking.

What runs afterwards

fsmes run-opc-agent     # subscribes and records
fsmes run-api           # dashboards at /dashboard

One session, held open. If it drops, the window it was not watching is reported as unknown and is not reconstructed later — so run it under a supervisor from day one (deploy).

One MES, several OPC servers

A plant whose line spans two servers sets MES_OPC_ENDPOINTS to a JSON list instead of the single endpoint:

MES_OPC_ENDPOINTS='[{"endpoint":"opc.tcp://a:49320","tag_map":"config/tag_map_a.json"},
                    {"endpoint":"opc.tcp://b:49320","tag_map":"config/tag_map_b.json"}]'

One agent process, one subscription per entry, each with its own tag map. Each server's owner needs the same five things and the same certificate step.

When their server goes away

It will. A switch reboots, a certificate expires, somebody unplugs the wrong port. The agent reconnects for ever, so nothing needs doing — but what the MES says about the gap is worth knowing before the first one happens, because it is the first thing an incumbent MES's operators will test.

Every machine on that endpoint reads disconnected, with since-when, on the floor tiles, the machine page, the line view, /equipment/connections and the fleet console; /health says how many. None of them shows the state the machine was in when the link died, and none of them shows down: for those minutes the MES has no state for the machine, and the seconds leave availability's denominator instead of counting against the machine.

The full story, including the one case it does not cover — an agent killed outright writes nothing — is in losing sight of a machine.

Which servers this has been tested against

Read compatibility before you promise anybody anything. As of 2026-09-10 the only third-party server tested is KEPServerEX, in a lab, with a trial licence; everything else is untested, and untested is stated as a fact rather than as a warning label. The client is asyncua, and the tag map is the only server-specific part — which is a reason to expect it to work, not evidence that it does.